OWNER’S MANUAL MODELS EASASD-10ASC, EASASD-11ASC EASASD-12ASC, EASASD-18ASC ELECTRONIC AIR CLEANERS IMPORTANT: PLEASE READ MANUAL BEFORE OPERAT
ohmmeter can be used. Always discharge the cell with a screw driver before testing with an ohmmeter. 1. With the ohmmeter set on its lowest
# Part Description EASASD-10 EASASD-11 EASASD-12 EASASD-18 1 On/Off Switch R1-0205 R1-0205 R1-0205 R1-0205 2 Safety Interlock Switch R1-
12 PROBLEM PROBABLE CAUSE REMEDY System fan is not on. Turn system fan on. Unit does not function correctly. Power light and performance indi-cat
Cleaning Record The collecting cells and prefilters must be cleaned on a regular basis for the Air Cleaner to function at its peak of efficien
NOTES: 14
ELECTRO-AIR CANADA 351 North Rivermede Road, Concord, Ontario, Canada L4K 3N2 Tel: (416) 213-5636 Fax: (416) 213-5593 Toll Free 1
IMPORTANT WIRING INFORMATION This Electronic Air Cleaner is equipped with an Air Proving Switch (APS). The recommended source for the input vol
CONTENTS Certified for shock and electrical fire hazard only. SAFETY CONSIDERATIONS Read and follow instructions carefully. Follow all local
area where they are attracted to a series of grounded plates. Pollutants are held in this section like a magnet until washed awa
Installation Location With Humidifier A humidifier should be installed in the furnace warm air duct. However, it may be installed in the
5 Fig. 5 — Air Cleaner Schematic (with Air Proving Switch) Electronic Air Cleaner Installation 1. Remove existing equipment filter. Thoroughly
Note: There may be some arcing or snapping sounds from the collecting cells. This is normal when the unit is new. In about 2 week
functions: 1. Turn Air Cleaner power switch OFF. 2. Turn off system fan. 3. Open access door. 4. Remove collecting cells from Air Cleaner. 5. R
4. Push the new light into the power box. 5. Connect the wiring to the LED terminals on the power board. P3 - red; P4 - black. Route the
without the transformer connected. Resistance should read above 20K ohms with an analog meter and above 4M ohms with a digital mete